Peregrine Industries - Specialists in high quality air filters that are designed to meet your needs.  Air filters for all types of Heating, Ventilation and  Air Conditioning (HVAC) systems and high purity products - paint spray booths filters, cleanroom filters, bio-safety and clean bench filters. FilterMedia
Home About Products technical section news updates and FilterMedia newsletter contact us  
 

 

Spraybooth

NEWSFLASH
(click to view)

Monthly Tech spotlight link TECH SPOTLIGHT
(click to view)

FilterMedia newsletter link
click to download


Air filters for all types of Heating, Ventilation and Air Conditioning (HVAC) systems.  High purity products for Gas Turbines, Paint Spray Booths, cleanrooms, bio-safety and clean benches.

World leading spray booths by GFS in the USA

 

AIR FILTERS TECHNICAL SECTION - Technical Issues

WORLDWIDE AIR FILTER TEST METHOD COMPARISON CHART

Newest USA Particle Size Test

In Approximation with older test standard

Regular USA Dust Spot Test

European Version Pf Regular Dust Spot Test

Proposed New European Particle Size Test

BS 3928

High Efficiency Particulate Air Filters Initial Efficiency A (Test Aerosol: NaCl)

ASHRAE 52.2-1999

Std. 52.2 Minimum Efficiency Reporting Value (MERV) (Test Aerosol: KCL)

ASHRAE 52.1 - 1992

ASHRAE 52.1 – 1992

DIN EN779 – 1993

CEN EN779 – 2002

Average Dust Spot Efficiency @450Pa

Average Arrestance @250Pa

Average Dust Spot Efficiency @450Pa

Average Arrestance @250Pa

Average Dust Spot Efficiency @450Pa

Average Arrestance @250Pa

Average Efficiency of only 0.4µm particles @450Pa (Test Aerosol: DEHS)

Average Arrestance @250Pa

Micron Size 0.3-10.0 µm

Ea>20%

Ea <20%

Ea>20%

Ea <20%

Ea>20%

Ea <20%

Micron size 0.4µm

 

Micron size 0.3 (0.6) µm

                     

MERV 20

NA

NA

           

EU 14 (A>99.999%)

MERV 19

NA

NA

           

EU 13 (A>99.99%)

MERV 18

NA

NA

           

EU 12 (A>99.97%)

MERV 17

NA

NA

           

EU 11 (A>99.9%)

MERV 16

NA

NA

           

EU 10 (A>95%)

MERV 15

> 95%

NA

> 95%

 

F9 (> 95%)

 

F9 (> 95%)

   

MERV 14

90 – 95%

> 98%

90 – 95%

 

F8 (90 - 95%)

 

F8 (90 - 95%)

   

MERV 13

80 – 90%

> 98%

80 – 90%

 

F7 (80 – 90%)

 

F7 (80 – 90%)

   

MERV 12

70 – 75%

> 95%

60 – 80%

 

F6 (60 – 80%)

 

F6 (60 – 80%)

   

MERV 11

60 – 65%

> 95%

             

MERV 10

50 – 55%

> 95%

40 – 60%

 

F5 (40 – 60%)

 

F5 (40 – 60%)

   

MERV 9

40 – 45%

> 90%

             

MERV 8

30 – 35%

> 90%

 

> 90%

 

G4 (> 90%)

 

G4 (> 90%)

 

MERV 7

25 – 30%

>90%

             

MERV 6

<20%

85 – 90%

 

80 – 90%

 

G3 (80 – 90%)

 

G3 (80 – 90%)

 

MERV 5

<20%

80 – 85%

             

MERV 4

<20%

75 – 80%

 

65 – 80%

 

G2 (65 – 80%)

 

G2 (65 – 80%)

 

MERV 3

<20%

70 – 75%

             

MERV 2

<20%

65 – 70%

              

MERV 1

<20%

< 65%

 

< 65%

 

G1 (< 65%)

 

G1 (< 65%)

 

 

If you have any questions or queries relating to the content of this page or any technical questions relating to air filters, spray booths, Peregrine Industries, Filtrair, Filtration Group or GFS or any product on this site, please contact us through our contacts page

 

Download Air Filter Test Method Comparison Chart in pdf format

 

Proud member of AARN

Proud member of NAFA

©Copyright Peregrine Industries Pty. Ltd. - 2007